Circuit Breaker
Meba insulator circuit breaker MBS
Product Description
Meba insulator circuit breaker MBS is mainly used in AC50/60Hz single pole 230V or two, three, four pole 400V voltage for overload and short-circuit protection as well as for un-frequent on-and-off switching electric equipment and lighting circuit under normal condition, the product is suitable for industry, business, building, residence, etc. It’s conformity with GB10963, IEC60898 standards.Meba insulator circuit breaker MBS
Standard | IEC60898 | |
Number of poles | 1P, 2P, 3P, 4P | |
Rated current(In) | 6, 10, 16, 20, 25, 32, 40, 50, 63 | |
Rated voltage(Un) | AC240/415V | |
Rated frequency | 50/60Hz | |
Tripping curve | B, C, D | |
Release action characteristics | Time delay | 1.13In>1h Non-trip |
1.45In<1h trip | ||
2.55In 1s-60S trip | ||
Instantaneous(Curve C) | 5In>0.1s Non-trip | |
10In<0.1s trip | ||
Magnetic releases operate | B curve:between 3 and 5In | |
C curve:between 5 and 10In | ||
D curve:between 10 and 15In | ||
Rated breaking capacity (Lcn) | 3000A | |
Endurance | >2500 | |
Circumstance temperature | -5 to +40°C | |
Electrical life | >6000times | |
Mechanical life | 20000 times | |
Tropical ration | Treatment 2(RH95%, at 55°C) | |
Protection degree | IP20 |
Meba insulator circuit breaker MBS
is mainly used in AC50/60Hz single pole 230V or two, three, four pole 400V voltage for overload and short-circuit protection as well as for un-frequent on-and-off switching electric equipment and lighting circuit under normal condition, the product is suitable for industry, business, building, residence, etc. It’s conformity with GB10963, IEC60898 standards.
Inquiry Form - lucy from Meba
If you would like a quotation or further information on this product, please fill in the form below and we will reply to you within 1 working day.