Meba mcb plug in circuit breaker MB436C
Product Description
Meba mcb plug in circuit breaker MB436C is nice in appearance, reasonable in structure, sound in feature and high in breaking capacity. Installed with standard din rail, it is convenient and easy in usage. It is mainly used in the line of AC 50/60Hz, rated working voltage to 240V/ 415V, and rated current up to 63A to protect against overload and short-circuit.Meba mcb plug in circuit breaker MB436C
Technical parameters:
Rated current In |
A |
1,2,3,4,6,10,16,20,25,32,40,50,63 |
||
Electrical features |
Poles |
1P,2P,3P,4P |
||
Rated voltage Ue |
V |
230/400 |
||
Insulation voltage Ui |
V |
500 |
||
Rated frequency |
50/60Hz |
|||
Rated breaking capacity |
A |
10000 |
||
Energy limiting class |
3 |
|||
Rated impulse withstand voltage (1.2/50)Uimp |
V |
6000 |
||
Dielectric test voltage at ind .Freq.for 1min |
kV |
2 |
||
Pollution degree 2 |
||||
Power loss per pole |
Rated current(A) |
Max power loss per pole (W) |
||
1,2,3,4,6,10 |
2 |
|||
16,20,25,32 |
3.5 |
|||
40,50,63 |
5 |
|||
Thermo-magnetic release Characteristic |
B,C,D |
|||
Mechanical features |
Electrical life 8000 |
|||
Mechanical life 20000 |
||||
Contact position indicator Yes |
||||
Protection degree IP40 |
||||
Reference temperature for Setting of thermal element |
°C |
30 |
||
Ambient temperature (with daily average≤35°C) |
°C |
-5…..+40
|
||
Storage temperature |
°C |
-25….+70 |
||
Installation |
Terminal connection type |
Cable /U-type busbar/pin-type busbar |
||
Terminal size top/bottom for cable |
mm2
|
25 |
||
AWG |
18-3 |
|||
Terminal size top/bottom for busbar |
mm2
|
25 |
||
AWG |
18-3 |
|||
Tightening torque |
N*m In-Ibs |
2.0 22 |
||
Mounting |
On DIN rail 35mm |
|||
Connection |
From top and bottom |
|||
Combination with occessories |
Auxiliary contact |
Yes |
||
Shunt release |
Yes |
|||
Under voltage release |
Yes |
|||
Alarm contact |
Yes |
Meba mcb plug in circuit breaker MB436C
- Meba mcb plug in circuit breaker MB436C is nice in appearance, reasonable in structure, sound in feature and high in breaking capacity. Installed with standard din rail, it is convenient and easy in usage.
- It is mainly used in the line of AC 50/60Hz, rated working voltage to 240V/ 415V, and rated current up to 63A to protect against overload and short-circuit.
- It can be used as infrequent on-and-off operation and changeover.
- It complies with standard GB10963 and IEC/EN60898.