Meba Circuit Breaker Protection Device NS-400N-3P
Product Description
Meba Circuit Breaker Protection Device NS-400N-3P NS series Compact MCCB the rated insulating voltage is 750V, suitable for AC 50Hz(60Hz), rated working voltage 690V or below, rated working current is 12.5A to 1250A of circuit.Meba Circuit Breaker Protection Device NS-400N-3P
Type | Pole No. | Rated insulating voltage(V) | Rated operating voltage(V) | Rated ultimate short circuit breaking capacity Icu(KA) at 380/415V | Rated services short circuit breaking capacity Ics at 380/415V(KA) | Operation performace | Utiliza-tim Category | |
ON | OFF | |||||||
NS-100N | 3, 4 pole | 750 | 690 and below | 25 | 25 | 1500 | 8500 | A |
NS-100H | 70 | 70 | ||||||
NS-100L | 150 | 150 | ||||||
NS-160N | 36 | 36 | 1000 | 7000 | ||||
NS-160H | 70 | 70 | ||||||
NS-160L | 150 | 150 | ||||||
NS-250N | 36 | 36 | 1000 | 7000 | ||||
NS-250H | 70 | 70 | ||||||
NS-250L | 150 | 150 | ||||||
NS-400N | 45 | 45 | 1000 | 4000 | ||||
NS-400H | 70 | 70 | ||||||
NS-400L | 150 | 150 | ||||||
NS-630N | 45 | 45 | 1000 | 4000 | ||||
NS-630H | 70 | 70 | ||||||
NS-630L | 150 | 450 | ||||||
NS-1250N | 3 pole | 50 | 37.5 | 1000 | 4000 | |||
NS-1600N | 50 | 37.5 |
Note:
1. The N-pole breaker has no protection which closing and opening with the other three poles.
2. The type of thermal magnetic for NS-400/630 has no four poles.
Trip unit main technical parameter:
Type | Rated Current In(A) | Note |
NS-100 | 12.5,16,20,25,32,40,50,63,80,100 | T adjustable(0.8-1In) M adjustable(5-10In) |
NS-160 | 16,20,25,32,40,50,68,80,100,125,160 | |
NS-250 | 160,180,200,225,250 | |
NS-400 | 315,350,400 | |
NS-630 | 400,500,630 | |
NS-1250 | 800,1000,1250 | T adjustable(0.8-1In) M fixed |
NS-1600 | 1000,1250,1600 |
Meba Circuit Breaker Protection Device NS-400N-3P
Application:
1. NS series Compact MCCB the rated insulating voltage is 750V, suitable for AC 50Hz(60Hz), rated working voltage 690V or below, rated working current is 12.5A to 1250A of circuit.
2. Used in distributing electric energy, and non-frequent breaking in the normal conditions, protecting the current & equipment from overload&under voltage, circuit breaker with rated frame current 400A or below can be used in motor’s non-frequent start, breaking during working, protecting motor from overload, short circuit&under-voltage.
3. The product conforms to IEC60947-2 standard.
Classification:
1. Installation way: Mounted vertically, Horizontal installation;
2. By use of circuit breaker usage: Distribution protection, Motor protection;
3. According to the mode of wiring points: Front panel wiring, Back panel wiring , Plug-in connection;
4. According to the mode of operation: direct operating handle, External turning the handle operations, electric operation;
5. By release type distinction: instantaneous action release (magnetic release), thermal + electromagnetic release (duplex); electronic release;
6. Poles Number: 3poles, 4poles;
Accessories | Rated operating voltage | Consumption | For type | |
Pick-up | Seal-in | |||
Shunt release(MX) | 24V | <10VA | <5VA | NS-100 ~ 630 |
100V | ||||
220/230V | ||||
380/400V | ||||
Under-voltage release(UN) | 220/230V | <10VA | <5VA | |
380/400V | ||||
Accessories | Rated operating voltage | Rated operating current | For type | |
AC12 | AC15 | |||
Auxiliary contact(OF) | 380/400V | 6 | 3 | NS-100 ~ 630 |
Alarm contact(AL) | 380/400V | 6 | 3 |
Rotary handle
-A. Direct rotary handle
Degree of protection:IP40
Function:
1) suitability for isolation
2) indication of three positions 0(off) I(on) and tripped
3) press ush to trip?button, can trip-free
4) visibility of and access to trip unit settings
5) the circuit breaker can be locked in the off position by one to three padlocks, diameter 5 to 8mm(not supplied)
-B. Extended rotary handle
Degree of protection:IP55
Function:
1) Suitability for isolation
2) Indication of three positions 0(off) I(on) and tripped
3) Visibility of and access to trip unit settings when the door is open
4) Door opening prevented when circuit breaker is on
5) The circuit breaker can be locked in the off position by one to three padlocks, diameter 5 to 8mm(not supplied). Locking prevents opening of the switchboard door
Installation: Circuit breaker may be mounted vertically, horizontally or flat on their back without any derating of characteristics.
Fix: Mounting on backplate, mounting on rails
Connection: Front panel connection, black panel connection, plug-in connection