Meba Electric Automation Moulded Case Switch NF63-CP
Product Description
Meba Electric Automation Moulded Case Switch NF63-CP NF series thermal magnetic type molded case circuit breaker, developed type mccb, included NF-CS, NF-SS, NF-CP, NF-SP, NF-HP, NF-CW series.Meba Electric Automation Moulded Case Switch NF63-CP
Parameters of NF-63 Moulded Case Circuit Breaker
Frame Current(A) | 63 | ||||||
Model | NF-63C | NF-63S | |||||
Rated Current in(A) | 10,16,20,32,40,50,63 | 10,16,20,32,40,50,63 | |||||
Poles | 2 | 3 | 4 | 2 | 3 | 4 | |
Rated Voltage Ue(V) | AC400 | ||||||
Rated Insulation Voltage Ui(V) | AC690 | ||||||
(KA)AC400 Short-Circuit Interrupting Capacity Icu/Ics | 10/5 | 35/20 | |||||
Operation Life(cycle) | Power on | 6000 | |||||
Power off | 9000 | ||||||
Dimensions(mm) | a | 50 | 75 | 100 | 50 | 75 | 100 |
b | 130 | 130 | |||||
c | 68 | 68 | |||||
ca | 90 | 90 | |||||
Weight(kg) | 0.45 | 0.65 | 0.45 | 0.65 | |||
Electrical-operation Device(MD) | • | • | |||||
External Rotary Handle | • | • | |||||
Automatic Tripping Device | thermal-magnetic | thermal-magnetic |
Meba Electric Automation Moulded Case Switch NF63-CP
1. NF series thermal magnetic type molded case circuit breaker, developed type mccb, included NF-CS, NF-SS, NF-CP, NF-SP, NF-HP, NF-CW series.
2. Rated working voltage 690V, 50HZ or 60HZ, and rated working current from 3A to 800A.
3. It mainly used in distributing electric energy and protect the electrical circuit and power equipment from damages caused by overload, short circuit or under-voltage in the distribution network.
4. It complies with IEC60947-2 and GB14048.2 standards.
Working Conditions and Mounting Environments
1. The altitude should be less than 2000m
2. The ambient medium temperature should within -5? to +40?
3. This moulded case circuit breaker is resistant to moisture, salt fog, nuclear radiation, and mildew
4. The maximum tilt angle is 22.5°
5. MCCB can still work reliably if the product is subjected to vibration from ships or earthquakes(4g)