Meba c65 elcb rcbo rccb earth leakage circuit breaker MBR136C
Product Description
Meba c65 elcb rcbo rccb earth leakage circuit breaker MBR136C is used for the protection against electrical leakage in the circuit of 50Hz or 60Hz, rated voltage single-phase 230V, 3 phase 400V, rated current up to 60A.Meba c65 elcb rcbo rccb earth leakage circuit breaker MBR136C
Frame class |
1–60A |
Rated working voltage |
240/415V |
Rated frequency |
50/60Hz |
Rated working current |
16202532405063A |
Rated residual operating current |
0.03,0.1,0.3,0.5A |
Rated residual un-operating current |
0.015,0.05,0.15,0.25A |
Sensibility |
A TypeAC Type |
Maximum operating time |
In t≤0.1s , 5In t≤0.04 |
Rated making and breaking capacity |
In≤50A 500A,In=63A 630A , In63A 1500A |
Limiting value of un-operating current |
6In |
Rated limiting short-circuit current |
3000A |
Pole number |
1/2/3/4P |
Mechanical life |
8000 |
Electric life |
4000 |
Basic Data:
Constrcution and Feature |
1)Protection against both overload and short circuit |
2)High short-circuit capacity |
3)Applicable to terminal and pin/fork type busbar connection |
4)Easy mounting onto 35mm DIN rail |
Technical Data |
4)Pole No.: 1 . 1P+N .2 . 3 . 3P+N . 4 / 30mA |
5)Rated Voltage : AC 230/400V~ |
6)Rated Current(A): 1,2,3,4,6,10,13,16,20,25,32,40,50,63 |
7)Tripping curve: B, C, D |
8)Rated short-circuit capacity(Icn): 6KA |
9)Rated frequency :50Hz/60Hz |
10)Enerygy limiting class : 3 |
11)Rated impulse withstand voltage: 6.2kV |
12)Electro-mechanical endurance : 4000 |
13)Connection terminal : srew terminal and pillar terminal with clamp |
14)Connection capacity : Rigid conductor up to 25mm2 |
15)Fastenning torque: 2.0Nm |
16)Installation: On symmetrical DIN rail 35mm /Panel Mounting |
17)Terminal Connection Height: 19mm |
Meba c65 elcb rcbo rccb earth leakage circuit breaker MBR136C
Application:
1.C65NLE RCBO is used for the protection against electrical leakage in the circuit of 50Hz or 60Hz, rated voltage single-phase 230V, 3 phase 400V, rated current up to 60A.
2.When somebody gets an electric shock or the residual current of the circuit exceeds the fixed value, the ELCB can cut off the power within the time.
3.It is automatically to protect the personal safety and preventing the equipment from the fault resulted by the residual current.
4.With this function, the ELCB can protect the circuit against overload and short circuit or can be used for the unfrequent switchover of the circuit under normal conditions.
5.It conforms to IEC61009 standard.
Performance & Usage
Circuit breaker is mainly suitable for overload and short protection. It is especially used for illumination and distribution. It is of pleasing out-look, light weight, reliable performance, high breaking capacity, quick trip. etc.